Vision Systems - Accessories

Hilscher - netTAP 100

Product features

  • Fieldbus to Fieldbus
  • Real-Time-Ethernet to Fieldbus
  • RS232/422/485 to Fieldbus or Real-Time-Ethernet
  • Master or Slave to Master or Slave
  • Own serial protocols with netSCRIPT language
  • USB service port
  • Memory card option for saving firmware and configuration
  • Din-rail mounting
Data Sheet download manual

Variants

DescriptionOrder no.Dimensions Weight HS-Code
Gateway netTAP 100-RE-EN3-90-029100 x 52 x 70 mm150 g8542 31 90

Important advice

Please read the manual thoroughly before you start operating the device!

General technical data

Description
Diagnostic Interface Mini USB
Display LINK
Rx/Tx
SYS, COM
Protocol specific
Configuration SYCON.net
Operating voltage 18 - 30 V / 130 mA at 24 V
Plug connector Mini COMBICON 2-pole
Operating temperature 0°C - 60°C
Mounting On top-hat rail DIN EN 60715
CE sign Yes
Emission CISPR 11 Class A
Noise immunity EN 61131-2: 2003
Protocol Cyclic Data
ASCII Master 2024 Byte I/O-Data
Slave 2024 Byte I/O-Datan
CANopen Master 7168 Byte I/O-Data
Slave 1024 Byte I/O-Data
CC-Link Slave 736 Byte I/O-Data
DeviceNet Master 7168 Byte I/O-Data
Slave 510 Byte I/O-Data
PROFIBUS Master 11472 Byte I/O-Data
Slave 488 Byte I/O-Data
EtherCAT Slave 400 Byte I/O-Data
Ethernet/IP Master 11520 Byte I/O-Data
Slave 1008 Byte I/O-Data
Modbus RTU Master 11520 Byte I/O-Data
Slave 11520 Byte I/O-Data
Modbus TCP Master 11520 Byte I/O-Data
Slave 11520 Byte I/O-Data
netSCRIPT Master 2048 Byte I/O-Data
Slave 2048 Byte I/O-Data
PROFINET-IO Slave 2048 Byte I/O-Data
POWERLINK Slave 2980 Byte I/O-Data
SERCOS III Slave 256 Byte I/O-Data